Psychrometric Chart
A psychrometric chart plots the properties of moist air, with dry-bulb temperature on the horizontal axis and humidity ratio on the vertical axis. Use this free chart to plot state points and process lines, and read the enthalpy, humidity ratio, dew point, wet-bulb temperature, and relative humidity of each point. Switch between Imperial and Metric units, and set the site elevation to correct for atmospheric pressure.
Last updated
How to read a psychrometric chart
The axes
- Dry-bulb temperature is on the horizontal axis (°F or °C). It is the temperature that a standard thermometer reads.
- Humidity ratio is on the vertical axis (lb/lb or g/kg). It is the mass of water vapor per unit mass of dry air.
The property lines
- Relative humidity lines are curves from 10% to 100%. The 100% curve is the saturation line, the upper-left edge of the chart.
- Wet-bulb temperature lines slope down to the right. Each line meets the saturation line where the dry-bulb and wet-bulb temperatures are equal.
- Enthalpy lines show constant total heat content (BTU/lb or kJ/kg of dry air). They are almost parallel to the wet-bulb lines.
- Specific volume lines are steep diagonals (ft³/lb or m³/kg). They show the volume of moist air per unit mass of dry air.
Reading a state point
Two independent properties fix a state point, for example dry bulb and wet bulb, or dry bulb and relative humidity. The state point is where their lines cross. From that point:
- Read horizontally across to the vertical axis for the humidity ratio.
- Move horizontally to the left until you reach the saturation line, and read the dew point.
- Follow the wet-bulb line up to the saturation line, and read the wet-bulb temperature.
- Follow the enthalpy line to its scale, and read the enthalpy.
In this chart, click to drop a point, or create a point and type its dry bulb and its wet bulb or relative humidity. Hover a point to read its properties.
Common HVAC processes
Sensible heating and cooling move a point horizontally, because the humidity ratio does not change. Cooling below the dew point also removes moisture, so the point moves left and down toward the saturation line. When two air streams mix, the mixed air is on the straight line between them, closer to the stream with the larger airflow.
For a step-by-step walkthrough, read How to read a psychrometric chart: lines, state points, and HVAC processes.
Frequently asked questions
What is a psychrometric chart?
A psychrometric chart is a graph of the properties of moist air at one atmospheric pressure. It ties together dry-bulb temperature, wet-bulb temperature, dew point, relative humidity, humidity ratio, enthalpy, and specific volume. When you know two independent properties, you can read all of the others from the chart.
Is this psychrometric chart free to use?
Yes. The chart runs in your browser, and you do not need an account or a sign-up to plot points, draw process lines, or read their properties.
How do I find the dew point on a psychrometric chart?
Start at the state point and move horizontally to the left, at constant humidity ratio, until you reach the saturation curve (100% relative humidity). The dry-bulb temperature at that point is the dew point.
Why does elevation change the chart?
Atmospheric pressure falls as elevation rises, and the properties of moist air depend on pressure. At the same dry-bulb temperature and relative humidity, air at a higher elevation has a higher humidity ratio and enthalpy. Set the site elevation in the chart toolbar to use the correct pressure.
How do I calculate coil or mixing loads with the chart?
Create a process line between two state points and enter its flow rate in CFM or L/s. The chart then shows the sensible, latent, and total heat for that process.
Can I use Metric (SI) units?
Yes. Use the IP and SI switch above the chart. IP shows °F, lb/lb, and BTU/lb. SI shows °C, g/kg, and kJ/kg.