Ductulator
A ductulator finds the duct size for an airflow. Use this free online ductulator to size round and rectangular galvanized steel ducts by airflow, velocity, and friction loss. Then find the fitting loss and the duct weight. The ductulator runs in your browser, and you do not need an account or a sign-up.
Last updated
How to use this ductulator
Size a duct
- Enter the Flow Rate of the duct.
- Enter a Max Velocity, a Max Pd (the friction loss per 100 ft), or both. To fit a duct below a ceiling or a beam, also enter a Max Height.
- For a lined duct, enter the Liner Thickness. The Sizing Delta is the step between the duct sizes that the ductulator tries. It is 2 in by default.
- Read the duct size, and its Pd, Velocity, Area, and Velocity Pressure. The ductulator shows the smallest size that meets your limits. When a round duct that meets your limits is taller than the Max Height, the ductulator sizes a rectangular duct.
Check a duct size
Under Shape, choose Round or Rectangle. Then enter the diameter, or the height and the width. The ductulator shows the friction loss, velocity, and velocity pressure of that duct at your flow rate. Select Reset to go back to the sized duct.
Find the fitting loss
Enter the Fitting Coefficient (C) of the fitting. The Fitting Loss is C × Vp, where Vp is the velocity pressure in the duct. Get C from the ASHRAE Duct Fitting Database or from the manufacturer.
Find the duct weight
Enter the Length of the duct and the Wall Thickness of the sheet metal. The Galvanized Steel Weight is the perimeter × the wall thickness × the length × the density of galvanized steel. It does not include seams, joints, reinforcement, hangers, or liner.
Units
This page shows Imperial units: CFM, ft/min, in. w.g. per 100 ft, in, ft, and lb.
Frequently asked questions
How does the ductulator calculate fitting loss?
Fitting loss = C × Vp. C is the loss coefficient of the fitting, and Vp is the velocity pressure in the duct. For standard air, Vp = 0.075 × (V ÷ 1097)² in. wg, with V in fpm. This is the same as (V ÷ 4005)². Get C from the ASHRAE Duct Fitting Database or from the manufacturer, and use the C value that refers to the velocity in this duct.
How does the ductulator calculate duct weight?
Weight = perimeter × wall thickness × length × density. The perimeter comes from the outside duct size: π × diameter for a round duct, or 2 × (width + height) for a rectangular duct. The density is 0.2904 lb/in³ (8.04 g/cm³) for galvanized steel, including the zinc coating. The weight does not include seams, joints, reinforcement, hangers, or liner.
What wall thickness should I enter?
Enter the sheet metal thickness of the gauge that your duct construction standard specifies for the duct size and pressure class. For example, 24 gauge galvanized steel has a nominal thickness of 0.0276 in (0.70 mm).
Which duct material does the ductulator use?
Galvanized steel. The friction loss uses a friction equation for galvanized steel duct, and the duct weight uses the density of galvanized steel.
Is this ductulator free to use?
Yes. The ductulator runs in your browser, and you do not need an account or a sign-up.