CFM Calculator

Find the supply airflow (CFM) that a space needs to remove its sensible cooling load. Enter the sensible load, the room temperature, the supply air temperature, and the site elevation. The calculator corrects for the thinner air at elevation.

Last updated

How to calculate supply CFM

Supply air removes a sensible load when it enters the room colder than the room air. The airflow that you need is:

CFM = Qs ÷ (1.10 × ΔT)

  • Qs is the sensible cooling load of the space in Btu/h.
  • ΔT is the room temperature minus the supply air temperature in °F.
  • 1.10 is 60 min/h × air density × specific heat for standard air at sea level.

Elevation correction

At elevation, the calculator multiplies 1.10 by the ratio of the site atmospheric pressure to the sea-level pressure. Thinner air carries less heat per cubic foot, so the same load needs more airflow.

Example

A space has a sensible load of 20,000 Btu/h, a room temperature of 75 °F, and a supply air temperature of 55 °F. ΔT is 20 °F. At sea level, the supply airflow is 20,000 ÷ (1.10 × 20) = 909 CFM. At 5,000 ft, the pressure ratio is about 0.832, so the supply airflow is 20,000 ÷ (1.10 × 0.832 × 20) = 1,093 CFM.

For a full walkthrough, read How to calculate CFM from a cooling load.

Frequently asked questions

What formula does this CFM calculator use?

Supply CFM = sensible load ÷ (1.10 × ΔT). ΔT is the room temperature minus the supply air temperature. At elevation, the calculator multiplies 1.10 by the ratio of the site atmospheric pressure to the sea-level pressure. HVAKR uses the same equation to size space supply airflow in its load calculations.

Why does the calculator use 1.10 and not 1.08?

Both numbers are rounded values of 60 × air density × specific heat. The 1.08 value comes from dry air at 0.075 lb/ft³ and 0.24 Btu/lb·°F. The ASHRAE Handbook of Fundamentals uses 1.10 for standard air. The difference is about 2%, and 1.10 gives slightly less airflow.

How does elevation change supply airflow?

Air is less dense at higher elevations, so each cubic foot of air carries less heat. At 5,000 ft, the atmospheric pressure is about 83% of the sea-level pressure, so the same sensible load needs about 20% more CFM.

What supply air temperature should I use?

Use the air temperature at the supply diffuser. A common cooling design supplies 55 °F air to a 75 °F room, a difference of 20 °F. A smaller difference needs more airflow. The supply air must be colder than the room, or the calculator shows no result.

Does the calculator check the latent load?

No. The calculator sizes supply airflow on the sensible load only. Make sure that the cooling coil also removes the latent load of the space.

Is this CFM calculator free to use?

Yes. The calculator runs in your browser, and you do not need an account or a sign-up.